| Applications |
 |
|
ASHRAE 52.2 MINIMUM EFFICIENCY REPORTING VALUE (MERV)
|
APPROXIMATE
AS1324 or ASHRAE. 52.1 RESULTS
|
APPROXIMATE AS1324 FILTER PERFORMANCE RATING
|
|
NO. 1
or
DUST SPOT EFFICIENCY
|
|
TYPICAL CONTROLLED CONTAMINANT
|
TYPICAL APPLICATION and LIMITATIONS
|
|
|
|
|
|
< 0.30 um Particle Size
Virus (unattached)
Carbon Dust
Sea Salt
All Combustion Smoke
Radon Progeny
|
Cleanrooms
Radioactive Materials
Pharmaceutica Manufacturing
Carcinogenic Materials
Orthopaedic Surgery
|
TYPICAL FILTERS FOR MERV 17 TO 20
|
|
|
|
|
|
|
|
|
|
H13 / H14 / U15 / U16
|
|
|
|
ASHRAE 52.2 MINIMUM EFFICIENCY REPORTING VALUE (MERV)
|
APPROXIMATE
AS1324 or ASHRAE. 52.1 RESULTS
|
APPROXIMATE AS1324 FILTER PERFORMANCE RATING
|
|
NO. 1
or
DUST SPOT EFFICIENCY
|
|
TYPICAL CONTROLLED CONTAMINANT
|
TYPICAL APPLICATION and LIMITATIONS
|
|
|
|
|
|
0.30 - 1.0 um Particle Size
All Bacteria
Most Tobacco Smoke
Droplet Nuclei (sneeze)
Cooking Oil
Most Smoke
Insecticide Dust
Copier Toner
Most Face Powder
Most Paint Pigments
|
Hospital Inpatient Care
General Surgery
Smoking Lounges
Superior Commercial Buildings
|
TYPICAL FILTERS FOR MERV 13 TO 16
|
|
|
|
|
|
|
|
|
|
|
|
ASHRAE 52.2 MINIMUM EFFICIENCY REPORTING VALUE (MERV)
|
APPROXIMATE
AS1324 or ASHRAE. 52.1 RESULTS
|
APPROXIMATE AS1324 FILTER PERFORMANCE RATING
|
|
NO. 1
or
DUST SPOT EFFICIENCY
|
|
TYPICAL CONTROLLED CONTAMINANT
|
TYPICAL APPLICATION and LIMITATIONS
|
|
|
70-75%
60-65%
50-55%
40-45%
|
|
|
1.0 - 3.0 um Particle Size
Legionella
Humidifier Dust
Lead Dust
Milled Flour
Coal Dust
Auto Emissions
Nebulizer Drops
Welding Fumes
|
Superior Residential
Better Commerical Buildings
Hospital Laboratories
|
TYPICAL FILTERS FOR MERV 9 TO 12
|
|
|
|
|
|
|
|
|
|
|
|
ASHRAE 52.2 MINIMUM EFFICIENCY REPORTING VALUE (MERV)
|
APPROXIMATE
AS1324 or ASHRAE. 52.1 RESULTS
|
APPROXIMATE AS1324 FILTER PERFORMANCE RATING
|
|
NO. 1
or
DUST SPOT EFFICIENCY
|
|
TYPICAL CONTROLLED CONTAMINANT
|
TYPICAL APPLICATION and LIMITATIONS
|
|
|
|
|
|
3.0 - 10.0 um Particle Size
Mold
Spores
Hair Spray
Fabric Protector
Dusting Aids
Cement Dust
Pudding Mix
Snuff
Powdered Milk
|
Commercial Buildings
Better Residential
Industrial Workplaces
Paint Booth Inlet Air
|
TYPICAL FILTERS FOR MERV 5 TO 8
|
|
|
|
|
|
|
|
|
|
|
|
ASHRAE 52.2 MINIMUM EFFICIENCY REPORTING VALUE (MERV)
|
APPROXIMATE
AS1324 or ASHRAE. 52.1 RESULTS
|
APPROXIMATE AS1324 FILTER PERFORMANCE RATING
|
|
NO. 1
or
DUST SPOT EFFICIENCY
|
|
TYPICAL CONTROLLED CONTAMINANT
|
TYPICAL APPLICATION and LIMITATIONS
|
|
|
|
75-80%
70-75%
65-70%
<65%
|
|
>10.0 um Particle Size
Pollen
Spanish Moss
Dust Mites
Sanding Dust
Spray Paint Dust
Textile Fibers
Carpet Fibers
|
Minimum Filtration
Residential
Window Air Conditioners
|
TYPICAL FILTERS FOR MERV 1 TO 4
|
|
|
|
|
|
|
|
|
|
|
|
Notes
1) A MERV for other than HEPA/ULPA filters also includes a test airflow rate, but is not shown here because it has no significance for the purposes of this table. Extract from Table E1, ASHRAE 52.2
2) Filters with a rating of F7 and above, should be pre-filtered with atleast a F4 filter. |
|
|
 |
|
|
|
|
|
|
|
|
|
|
|
|
Copyright Camfil Farr Australia 2008
|
|
|
|
|
|